Home Meters and converters of electrical network parameters Electrical converters:

- AC voltage and current converter

ПНС-652 - AC voltage and current converter

Choose a modification:

Order code:

ПНС-652
AA
Input signal range:
BB
Output signal range:

Number:

Available for order.

The PNS-652 converter is designed for linear conversion of AC voltage or AC current signals into a standardized analog DC current signal. It is used for monitoring electrical networks and installations, as well as for telemechanics and automation of power facilities and automated process control systems (APCS) of energy-intensive industrial sites across various industries.

Functions:

  • Linear conversion of AC voltage or current input signals into a standardized analog output signal: 0–5 mA, 0–20 mA, 4–20 mA, 0–10 V;
  • Complete galvanic isolation;
  • Slim housing with spring terminals.
Input signal:
  • single-phase
  • AC voltage (modifications)
  • AC current (modifications)
  • shunt
Analog output:
  • quantity: 1
  • 0..5 mА, 0..20 mА, 4..20 mА
  • 0..10 V
Power supply:
  • = 24 V, 30 mA
Seller

from

4 506

including VAT

Choose a modification and complete your order code

ПНС-2

ПНС-102

ПНС-652

ПНС-420

General information:

Type of power supply:

Single-phase

Single-phase

Single-phase

Single-phase

Input signal type:

AC voltage

AC voltage

AC voltage
AC current

AC voltage

Input signals:

Quantity inputs:

1

1

1

1

Ranges of possible input signals:

From 0 to 75 mV (from shunt) / R = 250 kΩ
From 0 to 10 V / R = 130 kΩ
From 0 to 15 V / R = 200 kΩ
From 0 to 60 V / R = 267 kΩ
From 0 to 100 V / R = 200 kΩ
From 0 to 150 V / R = 667 kΩ
From 0 to 250 V / R = 667 kΩ
From 0 to 500 V / R = 1.3 MΩ
From 0 to 750 V / R = 2.5 Ω

From 0 to 75 mV (from shunt) / R = 250 kΩ
From 0 to 10 V / R = 130 kΩ
From 0 to 15 V / R = 200 kΩ
From 0 to 60 V / R = 267 kΩ
From 0 to 100 V / R = 200 kΩ
From 0 to 150 V / R = 667 kΩ
From 0 to 250 V / R = 667 kΩ
From 0 to 500 V / R = 1.3 MΩ
From 0 to 750 V / R = 2.5 Ω

From 0 to 100 mA / R = 1 Ω
From 0 to 1 A / R = 0.1 Ω
From 0 to 2.5 A / R = 0.1 Ω
From 0 to 5 A / R = 0.022 Ω
From 0 to 75 mV (from shunt) / R = 250 kΩ
From 0 to 10 V / R = 1 MΩ
From 0 to 15 V / R = 3 MΩ
From 0 to 60 V / R = 600 кΩ
From 0 to 100 V / R = 850 кΩ
From 0 to 150 V / R = 1.4 MΩ
From 0 to 250 V / R = 2.3 MΩ
From 0 to 500 V / R = 5 МΩ

From 0 to 10 V / R = 50 kΩ
From 0 to 15 V / R = 150 kΩ
From 0 to 60 V / R = 300 kΩ
From 0 to 100 V / R = 500 kΩ
From 0 to 150 V / R = 750 kΩ
From 0 to 250 V / R = 1.2 МΩ
From 0 to 500 V / R = 2.5 МΩ

Limit of the basic combined measurement error:

0,4 %

0,4 %

0,4 %

0,4 %

Measurement and conversion period:

adjustable time: 0.5–6 seconds

no more 6 seconds

no more 6 seconds

Configurable: max 0.6 seconds

Ultimate load:

Repeated twice, duration up to 5 seconds

Repeated twice, duration up to 5 seconds

• an overvoltage of 5 times the nominal value for up to 5 seconds, for voltage levels up to 100 V.
• an overvoltage of 2 times the nominal value for up to 5 seconds, for voltage levels above 100 V.
• an overcurrent of 5 times the nominal value for up to 5 seconds, for current signals.

• an overvoltage of 5 times the nominal value for up to 5 seconds, for voltage levels up to 100 V.
• an overvoltage of 2 times the nominal value for up to 5 seconds, for voltage levels above 100 V.

Maximum input signal frequency:

1 kHz

Maximum: 1 kHz

-

-

Analog output signals:

Number of outputs:

1

1

1

1

Output type:

Active output

Active output

Active output

passive output

Ranges of possible output signals:

0 to 5 mA / R ≤ 2000 Ω
–5 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
–10 to 10 V / R ≤ 2 кΩ

0 to 5 mA / R ≤ 2000 Ω
–5 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
–10 to 10 V / R ≤ 2 кΩ

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

4 to 20 mA / R ≤ 500 Ω

Indication:

Digital display:

Not included

Not included

Not included

Not included

Electrical data:

Supply voltage:

Direct current: 24 V
Alternating current: 230 V

Direct current: 24 V
Alternating current: 230 V

Direct current: 24 V

Direct current: 24 V (current loop)

Power consumption:

Direct current: no more than 120 mА
Alternating current: ≤ 5.0 VА

Direct current: no more than 100 mА
Alternating current: ≤ 5.0 VА

Direct current: no more than 30 mА

Direct current: no more than 30 mА

Galvanic isolation:

• Complete. All nodes are isolated from each other
• Galvanic (electrical) isolation voltage not less than 2000  V

• Complete. All nodes are isolated from each other
• Galvanic (electrical) isolation voltage not less than 2000  V

• Complete. All nodes are isolated from each other
• Galvanic (electrical) isolation voltage not less than 2000  V

-

Corps:

Installation type:

for DIN rail mounting

for DIN rail mounting

for DIN rail mounting

for DIN rail mounting

Weight, not more than:

not more than 0.5 kg

not more than 0.2 kg

not more than 0.1 kg

not more than 0.1 kg

Case size (HxWxD):

95х100х110 mm

100х23х115 mm

94х7х64 mm

76х26х115 mm

Degree of protection:

IP30

IP30

IP20

IP20

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C