The BRG-12 galvanic isolation block is designed for:

  • 🛡 Galvanic protection of electrical circuits operating with standardized analog signals (current or voltage);
  • 🔄 Transmission and matching of signals between different segments of measurement, control, and monitoring systems;
  • Enhancing the reliability and accuracy of automation, SCADA, and industrial devices by eliminating the effects of transients, interference, and potential shifts.

The device provides galvanic isolation of the input signal from the output, ensuring effective separation of electrical circuits and improving the protection of sensitive equipment.

Functional Features:

  • 🔒 Single-channel galvanic isolation – complete separation of input and output signals;
  • 🛡 Signal protection against electromagnetic interference, overvoltage, and transients;
  • 🔄 Signal conversion and transmission without distortion of amplitude or waveform;
  • Stable operation even in the presence of industrial disturbances and potential differences between system segments;
  • 🏭 Suitable for industrial use – in SCADA systems, telemechanics, power engineering, and related industries.

Electrical Characteristics:

  • Number of channels: 1;
  • Input: 1 passive, standardized: Current: 0–5 mA, 0–20 mA, 4–20 mA; Voltage: 0–5 V, 0–10 V;
  • Output: 2 active, standardized: Current: 0–5 mA, 0–20 mA, 4–20 mA; Voltage: 0–5 V, 0–10 V;
  • 🛡 Galvanic isolation: complete electrical separation between input and output;
  • 🔋 Power supply: 24 V DC.
Input:
  • 1
  • passive
  • unified.
Output:
  • 2
  • active
  • unified.
Power supply:
  • = 24 V
  • 125mA.
Seller

6 936

including VAT

Choose a modification and complete your order code

BRG-12

Input signals:

Quantity inputs:

1

Input type:

passive

Possible input signal ranges/load resistance:

0 to 5 mA / R = 200 Ohm
0 to 20 mA / R ≤ 50 Ohm
4 to 20 mA / R ≤ 50 Ohm
0 to 10 V / R ≥ 20kOhm

Limit of the basic combined measurement error:

± 0,2 %

Output signals:

Quantity outputs:

2

Output type:

active

Ranges of possible output signals/load resistance:

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

Galvanic isolation:

• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 1500 V.

Electrical data:

Supply voltage:

Direct current: 24 V

Power consumption:

Direct current: no more than 125 mA

Corps:

Installation type:

on DIN rail

Case size (HxWxD):

75х26х120 mm

Weight, not more than:

0,23 kg

Degree of protection:

IP20