МІК-111
МІК-111
Regulation type:
ON/OFF
Three-position
Analog PID controller
Pulse PID controller
PWM PID controller
ON/OFF
Three-position
Analog PID controller
Pulse PID controller
PWM PID controller
Number of independent regulators:
1
1
Additional features:
Signaller
Converter
Signaller
Converter
Quantity of analog inputs:
1
1
Output type:
unified: passive
thermal resistance: three-wire connection
unified: passive
thermal resistance: three-wire connection
Types of input sensors and signals:
0-5 mA, 0-20 mA, 4-20 mA
0-2 V, 0-10 V, 0-75 mV, 0-200 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100
Type: K,L,J,S,B,T,A-1
0-5 mA, 0-20 mA, 4-20 mA
0-2 V, 0-10 V, 0-75 mV, 0-200 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100
Type: K,L,J,S,B,T,A-1
Limit of the basic combined measurement error:
≤ 0.2
≤ 0.2
Рolling cycle time:
up to 0.1
up to 0.1
Galvanic isolation:
• Input isolated from other circuits.
• Input isolated from other circuits.
Switching to another sensor type:
User-configurable, calibration required
User-configurable, calibration required
Quantity of discrete inputs:
Not included
Not included
Number of outputs:
1
1
Output type:
active
active
Ranges of possible output signals:
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
The limit of the main combined error of the output signal formation:
≤ 0.2 %
≤ 0.2 %
Quantity of discrete outputs:
2
2
Types of discrete outputs:
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
Data exchange interface:
RS-485
RS-485
Data exchange protocol:
Modbus RTU
Modbus RTU
Indication type:
Seven-segment, digital
Seven-segment, digital
Indication accuracy:
Four categories
Four categories
Supply voltage:
Alternating current: 230 V
Direct current: 24 V
Alternating current: 230 V
Direct current: 24 V
Power consumption:
Alternating current: no more than 6.5 VA
Direct current: no more than 180 mA
Alternating current: no more than 6.5 VA
Direct current: no more than 180 mA
Availability of a built-in power supply for inputs:
Yes, optional, if specified in the order
= 24 V, 25 mА
Not included
Non-volatile memory:
Yes, EEPROM
Yes, EEPROM
Galvanic isolation:
• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V
• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V
Installation type:
Shield
DIN-rail
Case size (HxWxD):
48х96х162 mm
94х106х58 mm
Weight, not more than:
no more than 0.35 kg
no more than 0.35 kg
Degree of protection:
IP30
IP30
Ambient temperature:
-40 °C to +70 °C
-40 °C to +70 °C