Home Normalizing converters Inductive:

- Mutual inductance conversion unit with indication

BPVІ-10 - Mutual inductance conversion unit with indication

Choose a modification:

Order code:

BPVІ-10
AA
Type of first input signal:
BB
Output signal type:
U
Supply voltage:

Number:

Available for order.

Mutual inductance signal conversion unit with galvanic isolation:

  • Designed for continuous proportional conversion of the signal from mutual inductance sensors based on differential transformer, into unified current signals 4...20 mA, 0...20 mA, 0...5 mA and voltage 0...10 V.
  • Used to work with the following devices: manometer (pressure measurement), differential manometer (pressure difference measurement), vacuum gauge (vacuum measurement), manovacuum gauge (overpressure and liquefied gas pressure measurement), barometer (measurement of small overpressures up to 40 kPa) (Measurement of small pressures and vacuums).
  • Input signal measurement range: 0 - 10 mH; -10 - 0 - +10 mH.
  • Power supply: ~(220±22)V, (50±1)Hz.
  • Screw terminal block.
Inputs:
  • quantity: 1
  • mutual inductance
  • 0 - 10 mH
  • -10 - 0 - +10 mH
Outputs:
  • 1
  • active
  • 0-5mA, 0(4)-20mA, 0-10V.
Power supply:
  • = 24 V, 120mA
  • ~230V, 5VA
Discrete outputs:
  • quantity: 2
  • OK transistor: up to 40V, 100mA
  • closing relay: up to 230V, 5A.
Interfaces:
  • RS-485
  • Modbus RTU protocol.
Assembling:
  • on DIN rail
  • 115х100х110 mm.
Seller

from

12 354

including VAT

Choose a modification and complete your order code

BPVІ-1

BPVІ-10

Input signals:

Quantity inputs:

1

1

Input type:

Four-wire connection

Four-wire connection

Ranges of possible input signals:

0-10 mH
-10 - 0 - +10 mH

0-10 mH
-10 - 0 - +10 mH

Limit of the basic combined measurement error:

± 0,25 %

± 0,25 %

Measurement and conversion period:

0,01 second

0,01 second

Analog output signals:

Number of outputs:

1

1

Output type:

active

active

Ranges of possible output signals:

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

Discrete output signals:

Availability of discrete outputs:

No

Yes

Quantity of discrete outputs:

not included

two

Types of discrete outputs:

not included

• Transistor OK: up to 40V, 100mA
• Switching relay: up to 230V, 8A

Interfaces:

Data exchange interface:

not included

RS-485

Data exchange protocol:

not included

Modbus RTU

Indication:

Digital display:

No

Seven-segment

Electrical data:

Supply voltage:

Direct current: 24 V
Alternating current: 230 V

Direct current: 24 V
Alternating current: 230 V

Power consumption:

Direct current: no more than 120 mA
Alternating current: no more than 5 VA

Direct current: no more than 200 mA
Alternating current: no more than 6 VA

Non-volatile memory:

not included

not included

Galvanic isolation:

• Full. All components of the device are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.

• Full. All components of the device are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.

Corps:

Installation type:

on DIN rail

on DIN rail

Case size (HxWxD):

96х100х110 mm

96х100х110 mm

Weight, not more than:

0,5 kg

0,5 kg

Degree of protection:

IP30

IP30

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C