Home Manual signal transmitters Universal: manual control units:

- Manual control unit, universal

БРУ-110 - Manual control unit, universal

Choose a modification:

Order code:

БРУ-110
AA
Type of the first analog input signal:
ВВ
Type of second analog input signal:
СС
Analog output signal type:
U
Supply voltage:

Number:

Available for order.

The BRU-110 device is intended for manual or automatic control of various types of actuators (analog or pulse) or a pulse type signal generator ("more" or "less") and analog type (0..5 mA, 0(4)…20 mA or 0…10 V). In automatic mode, the BRU-110 transmits a signal from a control device or controller to the actuator, and in manual mode, depending on the type of actuator, it generates discrete (pulse) signals "more" or "less" or unified signals (0..5 mA, 0(4)…20 mA or 0…10 V), the control is performed by the user from the front panel.

Analog input:
  • quantity: 2
  • 0..5mA, 0(4)..20mA, 0..10V
Analog output:
  • quantity: 1
  • 0..5mA, 0(4)..20mA, 0..10V
Inputs:
  • quantity 4
  • MANUAL/AUTO switching
  • "More" and "Less"
  • =24V, NPN
Outputs:
  • quantity 4
  • changeover relays
  • functional
Power supply:
  • = 24 V, 180mA
  • ~230V, 9VA
Interfaces:
  • RS-485
  • Modbus RTU protocol
Seller

15 480

including VAT

БРУ-110

БРУ-110Н

БРУ-10

Analog input signals:

Quantity of analog inputs:

2

2

2

Possible input signal ranges/load resistance:

0 to 5 mA / R = 400 Ohm
0 to 20 mA / R ≤ 100 Ohm
4 to 20 mA / R ≤ 100 Ohm
0 to 10 V / R ≥ 25kOhm

0 to 5 mA / R = 400 Ohm
0 to 20 mA / R ≤ 100 Ohm
4 to 20 mA / R ≤ 100 Ohm
0 to 10 V / R ≥ 25kOhm

0 to 5 mA / R = 400 Ohm
0 to 20 mA / R ≤ 100 Ohm
4 to 20 mA / R ≤ 100 Ohm
0 to 10 V / R ≥ 25kOhm

Limit of the basic combined measurement error:

≤ 0.2 %

≤ 0.2 %

≤ 0.2 %

Measurement and conversion period:

0.1 seconds

0.1 seconds

0.1 seconds

Analog output signals:

Quantity of analog outputs:

1

1

1

Ranges of possible output signals/load resistance:

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

The limit of the main combined error of the output signal formation:

±0,2%

±0,2%

±0,2%

Input signals:

External MANUAL/AUTO switching

Yes
"More" and "Less" signals from the controller

Yes
"More" and "Less" signals from the controller

Yes
"More" and "Less" signals from the controller

Input type:

=24 V, NPN

=24 V, NPN

=24 V, NPN

Output signals:

Quantity of outputs:

4

4

4

Output types:

Transfer relays

Transfer relays

Transfer relays

Load type:

Direct current: 6..34 V, 250 mА
Alternating current: 12..242 V, 250 mA

Direct current: 6..34 V, 250 mА
Alternating current: 12..242 V, 250 mA

Direct current: 6..34 V, 250 mА
Alternating current: 12..242 V, 250 mA

Indication:

Indication type:

Seven-segment, four digits
Bar graph

Seven-segment, four digits
Bar graph

Seven-segment, four digits
Bar graph

Indication accuracy:

± 0,01 %

± 0,01 %

± 0,01 %

Interfaces:

Interface type:

RS-485

RS-485

RS-485

Data exchange protocol:

Modbus RTU

Modbus RTU

Modbus RTU

Corps:

Installation type:

Shield

DIN rail

Shield

Case size (HxWxD):

96х96х120 mm

110х160х58 mm

96х96х120 mm

Degree of protection:

IP30

IP30

IP30

Electrical data:

Supply voltage:

Direct current: 24 V
Alternating current: ~230 V

Direct current: 24 V
Alternating current: ~230 V

Direct current: 24 V
Alternating current: ~230 V

Power consumption:

Direct current: no more than 180 mА
Alternating current: ≤ 8.0 VА

Direct current: no more than 200 mА
Alternating current: ≤ 8.5 VА

Direct current: no more than 180 mА
Alternating current: ≤ 8.0 VА

Galvanic isolation:

• Complete. All nodes are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.

• Complete. All nodes are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.

• Complete. All nodes are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C