Home Normalizing converters Thermosensor signals, microprocessor:

- Universal normalizing converter, single-channel

NPM-12 - Universal normalizing converter, single-channel

Choose a modification:

Order code:

NPM-12
AA
Input signal type:
CC
Output signal type:

Number:

Available for order.
  • Universal standard converter NPM-12, - is designed to convert temperature values ​​measured by thermocouples or resistance thermometers or standardized signals (pressure, flow) into universal current signals 4...20 mA, 0...20 mA, 0...5 mA and voltage 0...10 V.
  • The converter allows switching between different types of sensors without the need for calibration.
  • Configured using the MIC-Programmer software package via one of the built-in USB interfaces. Configuration parameters are stored in independent memory.
  • Provides complete galvanic isolation (protection) of all device nodes. Can be used as a galvanic isolation device.
Inputs:
  • quantity: 1
  • unified signals
  • voltage
  • resistance temperature transducers
  • thermocouples.
Analog outputs:
  • quantity: 1
  • unified signals.
Power supply:
  • = 24 V, 60mA.
Interfaces:
  • USB (configuration).
Assembling:
  • on DIN rail
  • 100х23х115 mm.
Seller

from

5 346

including VAT

Choose a modification and complete your order code

NPM-12

NPM-12

Input signals:

Quantity inputs:

1

1

Input type:

passive

passive

Ranges of possible input signals:

0-5 mA, 0-20 mA, 4-20 mA, -5-5 mA, -20-20 mA
0-10 V, 0-100 mV, -10-10 V, -100-100 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,N,J,S,R,B,T,E,A-1, A-2, A-3
0-150 Ohm, 0-300 Ohm, 0-1200 Ohm, 0-2500 Ohm

0-5 mA, 0-20 mA, 4-20 mA, -5-5 mA, -20-20 mA
0-10 V, 0-100 mV, -10-10 V, -100-100 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,N,J,S,R,B,T,E,A-1, A-2, A-3
0-150 Ohm, 0-300 Ohm, 0-1200 Ohm, 0-2500 Ohm

Limit of the basic combined measurement error:

± 0,2 %
± 0.2 mm

± 0,2 %

Measurement and conversion period:

0,1 second

0,1 second

Analog output signals:

Number of outputs:

1

1

Output type:

active

active

Ranges of possible output signals:

0 to 5 mA (special version, reconfiguration to other signal types will be impossible)
0 to 20 mA
4 to 20 mA
0 to 10 V

0 to 5 mA (special version, reconfiguration to other signal types will be impossible)
0 to 20 mA
4 to 20 mA
0 to 10 V

Discrete output signals:

Availability of discrete outputs:

No

No

Quantity of discrete outputs:

not included

not included

Types of discrete outputs:

not included

not included

Interfaces:

Data exchange interface:

USB

USB

Data exchange protocol:

Modbus RTU

Modbus RTU

Indication:

Digital display:

No

No

Electrical data:

Supply voltage:

Direct current: 24 V

Direct current: 24 V

Power consumption:

Direct current: no more than 60 mA

Direct current: no more than 60 mA

Non-volatile memory:

Yes, EEPROM, NVRAM

Yes, EEPROM, NVRAM

Galvanic isolation:

• Full. All components of the device are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.

• Partially. The input and power supply of the device are isolated from each other. The output is not isolated.
• Galvanic isolation voltage is not less than 500 V.

Corps:

Installation type:

on DIN rail

on DIN rail

Case size (HxWxD):

99х13х115 mm

91x15x64 mm

Weight, not more than:

0.3 kg

0.3 kg

Degree of protection:

IP20

IP20

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C