Home I/O modules Discrete input modules:

- Discrete input module

RIO-5N-DI32 - Discrete input module

Order code:

RIO-5N-DI32
U
Supply voltage:

Number:

Available for order.

The RIO-5N-DI32 discrete input module is designed to collect data from built-in inputs (discrete sensors) with subsequent transmission to the RS-485 network. The module is controlled by a PLC, panel controller, PC or other controlling device.

Main features of the module:

  • 32 discrete input channels, group isolation;
  • Types of input signals: signals: transistor keys p-n-p, n-p-n type;
  • Input supply voltage: =12V, =24V;
  • Device supply voltage: =12V, =24V, ~230V  .
Inputs:
  • quantity: 32
  • PNP/NPN type
  • =12В, =24В
Interfaces:
  • RS-485
  • Modbus RTU protocol.
Power supply:
  • =12В, ≤ 440 mА
  • =24В, ≤ 140 mА
  • ~220В, ≤ 5.3 VА
Seller

from

9 936

including VAT

Choose a modification and complete your order code

RIO-5N-DI32

Discrete input signals:

Quantity of discrete inputs:

32

Maximum pulse frequency:

5 Hz

Input current (input consumption), no more:

=12V, ≤10 mА
=24V, ≤10 mА

Trigger signal levels:

Logical "0" signal – "DISABLED" state: 0-3.5V (if 12V); 0-7V (if 24V)
Сигнал логічної "1" – стан "УВІМКНЕНО": 9-15V (if 24V); 18-30V (if 24V)

Connectable sensors:

• Switching devices (contacts of buttons, switches, reed switches, relays, etc.)
• n-p-n-type with open collector output
• p-n-p-type

Interfaces:

Data exchange interface:

RS-485

Data exchange protocol:

Modbus RTU

Electrical data:

Supply voltage:

Direct current: 12 V
Direct current: 24 V
Alternating current: 230 V

Power consumption:

Direct current: no more than: 440mA (for 12V), 220mA (for 24V)
Alternating current: no more than: 5.3 VА

Availability of a built-in power supply for inputs:

Yes (one per group of 8 inputs), 12V or 24V, ≤ 40 mA

Galvanic isolation:

• The inputs are connected in 2 groups of 8 channels and are galvanically isolated from other inputs and other circuits.
• The interface is galvanically isolated from inputs and other circuits.
• Galvanic isolation voltage is not less than 500 V.

Corps:

Installation type:

DIN rail

Case size (HxWxD):

132х153х57 mm

Weight, not more than:

0,18 kg

Degree of protection:

IP20

Operating conditions:

Ambient temperature:

-40 °C to +70 °C