Eight-channel thermostat МТР-8Н

МТР-8 Eight-channel thermostat МТР-8Н

Choose a modification:

Order code:

МТР-8
AA
Range from 1 to 8 - input signals:
E
Analog output range:
D
Type of output discrete signals:
U
Power Supply Voltage:

Number:

Available for order.

MTR-8 is an industrial eight-channel temperature controller with PID control functionality. It is designed for simultaneous measurement, indication, control, and remote monitoring of up to eight technological parameters—such as temperature, pressure, humidity, flow, level, and other physical quantities—across various industrial applications, depending on the type of connected sensor. The device generates output control signals accordingly.

⚙️ Functional Capabilities:

📊 Measurement and Indication:

  • 8 independent universal group-type inputs for measuring temperature or other physical quantities (pressure, humidity, flow, level, etc.) via sensors with standardized current or voltage outputs
  • Sensor type change is possible, but requires recalibration and repositioning of input board jumpers
  • Real-time digital display of measured values
  • Independent input scale configuration
  • Digital filtering and input signal correction
  • Signal connection via external terminal block of the control unit KBZ

📈 Control Modes:

  • Eight separate and independent controllers
  • Supports maintaining a stable parameter value based on user-defined setpoints
  • Control types implemented:
    • PID control: analog, pulse, and PWM
    • Two-position (ON/OFF) and three-position control
  • Manual control from the device’s front panel
  • Generation of control signals for actuators (e.g., electric valves, solid-state relays, frequency converters)

🚨 Alarming:

  • Alarm function for parameter deviations beyond preset limits, with triggering of discrete outputs
  • Linear conversion of the input signal to a standardized analog output signal

🔄 Additional Features:

  • Support for expansion modules
  • Mathematical operations
  • Communication interface: RS-485
  • Supported protocols: Modbus RTU
Input signals:
  • quantity: 8
  • unified signals
  • voltage
  • resistance temperature transducers
  • thermocouples
Discrete outputs:
  • quantity: base-8 and up to 16 expansion modules
  • OK transistor: up to 40V, 100mA
  • closing relays: up to 230V, 5A.
Analog output:
  • quantity: up to 4
  • unified signals
Interfaces:
  • RS-485
  • Modbus RTU protocol
Power supply:
  • ~ 100 V to ~ 242 V, 8.5 VA
  • = 18 V to 36 V, 300 mА
Assembling:
  • DIN rail
  • 110х160х58 mm
Seller

from

17 778

including VAT

Choose a modification and complete your order code

МТР-138

МТР-8

МТР-8

General information:

Regulation type:

ON/OFF
Three-position
Analog PID controller
Pulse PID controller
PWM PID controller

ON/OFF
Three-position
Analog PID controller
Pulse PID controller
PWM PID controller

ON/OFF
Three-position
Analog PID controller
Pulse PID controller
PWM PID controller

Number of independent regulators:

8

8

8

Additional features:

Signaller
Converter
Mathematical functions

Signaller
Converter
Mathematical functions
Expansion module support

Signaller
Converter
Mathematical functions
Expansion module support

Analog input signals:

Quantity of analog inputs:

8
group entry

8
group entry

8
group entry

Output type:

unified: passive
thermal resistance: three-wire connection

unified: passive
thermal resistance: three-wire connection

unified: passive
thermal resistance: three-wire connection

Types of input sensors and signals:

0-5 mA, 0-20 mA, 4-20 mA
0-75mВ, 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt1000
Type: K,L,J,S,B,T,A-1
0-1000 Ohm

0-5 mA, 0-20 mA, 4-20 mA
0-75mВ, 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,T,A-1

0-5 mA, 0-20 mA, 4-20 mA
0-75mВ, 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100
Type: K,L,J,S,B,T,A-1

Limit of the basic combined measurement error:

≤ 0.2

≤ 0.2

≤ 0.2

Рolling cycle time:

up to 0.1

up to 0.1

up to 0.1

Galvanic isolation:

• Group. Inputs are isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Group. Inputs are isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Group. Inputs are isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

Switching to another sensor type:

User-configurable, calibration required
Group input, one type for all inputs

User-configurable, calibration required
Group input, one type for all inputs

User-configurable, calibration required
Group input, one type for all inputs

Discrete input signals:

Quantity of discrete inputs:

Not included

• Base model: Not included
• With expansion module: up to 16

• Base model: Not included
• With expansion module: up to 16

Trigger signal levels:

Not included

• Logical "0" signal - DISABLED state: 0-7 V
• Logical "1" signal - ON state 18-30 V

• Logical "0" signal - DISABLED state: 0-7 V
• Logical "1" signal - ON state 18-30 V

Input consumption:

Not included

≤ 10 mА

≤ 10 mА

Analog output signals:

Number of outputs:

up to 4 (option)

• Base model: 1
• With expansion module: up to 4

• Base model: 1
• With expansion module: up to 4

Output type:

active

active

active

Ranges of possible output signals:

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

The limit of the main combined error of the output signal formation:

≤ 0.2 %

• Base model: ≤ 0.2 %
• With expansion module: ±0,4 %

• Base model: ≤ 0.2 %
• With expansion module: ±0,4 %

Discrete output signals:

Quantity of discrete outputs:

8

• Base model: 8
• With expansion module: up to 24

• Base model: 8
• With expansion module: up to 24

Types of discrete outputs:

• NPN transistor: up to 40V, 100mA
• Closing relay: up to 230V, 5A

• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid state relay: up to 60V, 1.0AAC/ADC
• Opto-triac: 600V, then 50mA

• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid state relay: up to 60V, 1.0AAC/ADC
• Opto-triac: 600V, then 50mA

Interfaces:

Data exchange interface:

RS-485

RS-485

RS-485

Data exchange protocol:

Modbus RTU

Modbus RTU

Modbus RTU

Indication:

Indication type:

Seven-segment, digital

Seven-segment, digital

Seven-segment, digital

Indication accuracy:

Four categories

Four categories

Four categories

Electrical data:

Supply voltage:

Alternating current: 230 V
Direct current: 24 V

Alternating current: 230 V
Direct current: 24 V

Alternating current: 230 V
Direct current: 24 V

Power consumption:

Alternating current: no more than 5.8 VA
Direct current: no more than 250 mA

Alternating current: no more than 8.5 VA
Direct current: no more than 250 mA

Alternating current: no more than 8.5 VA
Direct current: no more than 250 mA

Availability of a built-in power supply for inputs:

Not included

Not included

Not included

Non-volatile memory:

Yes, EEPROM

Yes, EEPROM

Yes, EEPROM

Galvanic isolation:

• All device components are isolated from each other. Group isolation of inputs.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V

• All device components are isolated from each other. Group isolation of inputs.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V

• All device components are isolated from each other. Group isolation of inputs.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V

Corps:

Installation type:

Shield

Shield

DIN-rail

Case size (HxWxD):

96х96х135 mm

96х96х135 mm

110х160х58 mm

Weight, not more than:

no more than 1.0 kg

no more than 1.0 kg

no more than 0.5 kg

Degree of protection:

IP30

IP30

IP30

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C