Touch operator panels Weintek
I/O modules
Spark protection barrier
Recorders and archivers
Meters and converters of electrical network parameters
Counters, timers, tachometers
Liquid level indicators and regulators
Programmed logical controllers
Manual signal transmitters
Technological signaling devices
Power supplies
Codesys PLC controllers
Galvanic isolation and branching blocks
Communication interface converters and amplifiers
Analytical instruments
Switching blocks
Control and protection units
GSM communication routers / modems
Dual-channel microprocessor position controller
МІК-302-К4
Regulation type:
ON/OFF
Three-position
Analog P - controller
Number of independent regulators:
2
Additional features:
Signaller
Converter
Mathematical functions
Quantity of analog inputs:
2
Output type:
unified: passive
thermal resistance: three-wire connection
Types of input sensors and signals:
0-5 mA, 0-20 mA, 4-20 mA, -5-5 mA, -20-20 mA
0-10 V, 0-100 mV, -10-10 V, -100-100 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,N,J,S,R,B,T,E,A-1, A-2, A-3, A, C
0-150 Ohm, 0-300 Ohm, 0-1200 Ohm, 0-2500 Ohm
Limit of the basic combined measurement error:
≤ 0.2
≤ 0.4 % (when switching to another sensor type, without calibration)
Рolling cycle time:
up to 0.1
Galvanic isolation:
• Input isolated from other circuits.
Switching to another sensor type:
User-selectable sensor type switching. No calibration required.
Quantity of discrete inputs:
2
Trigger signal levels:
• Logical "0" signal - DISABLED state: 0-7 V
• Logical "1" signal - ON state 18-30 V
Input consumption:
≤ 10 mА
Number of outputs:
2 (option)
Output type:
active
Ranges of possible output signals:
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
The limit of the main combined error of the output signal formation:
≤ 0.2 %
Quantity of discrete outputs:
up to 2
Types of discrete outputs:
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A (up to 2)
• Opto-triac output: up to 300 V, 0.7 A
• SSR relay: 0...6 V, 20 mА
Data exchange interface:
RS-485
USB
Data exchange protocol:
Modbus RTU
Indication type:
Seven-segment, digital
Indication accuracy:
Four categories
Supply voltage:
Alternating current: 230 V
Direct current: 24 V
Power consumption:
Alternating current: no more than 4.0 VA
Direct current: no more than 200 mA
Availability of a built-in power supply for inputs:
Not included
Non-volatile memory:
Yes, EEPROM
Galvanic isolation:
• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V
Installation type:
Shield
Case size (HxWxD):
48х96х135 mm
Weight, not more than:
no more than 0.3 kg
Degree of protection:
IP30
Ambient temperature:
-40 °C to +70 °C