Touch operator panels Weintek
Controllers (PID, ON/OFF)
I/O modules
Spark protection barrier
Recorders and archivers
Meters and converters of electrical network parameters
Counters, timers, tachometers
Liquid level indicators and regulators
Programmed logical controllers
Manual signal transmitters
Technological signaling devices
Power supplies
Codesys PLC controllers
Normalizing converters
Galvanic isolation and branching blocks
Communication interface converters and amplifiers
Analytical instruments
Switching blocks
Control and protection units
GSM communication routers / modems
Indicator - measuring device for technological parameters with bar graph
ІТМ-122
Device type:
Technological indicator
Additional features:
Input signal conversion
Alarms
Mathematical functions
Quantity of analog inputs:
2
Types of input sensors and signals:
0-5 mA, 0-20 mA, 4-20 mA
0-75mВ , 0-200 mВ , 0-2 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ
Limit of the basic combined measurement error:
≤ 0.2 %
Рolling cycle time:
up to 0.1 seconds
Galvanic isolation:
• Input isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.
Switching to another sensor type:
User-configurable, calibration required
Quantity of discrete inputs:
2
Trigger signal levels:
Logical "0" signal – "DISABLED" state: from 0 to 7 V, negative polarity
Сигнал логічної "1" – стан "УВІМКНЕНО": from 18 to 30 V, negative polarity
Input consumption:
≤ 10 mA
Number of outputs:
1
Output type:
active
Ranges of possible output signals:
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
The limit of the main combined error of the output signal formation:
≤ 0.2 %
Quantity of discrete outputs:
4
Types of discrete outputs:
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Opto-triac: up to 300 V, 0.7 A
Data exchange interface:
RS-485
Data exchange protocol:
Modbus RTU
Indication type:
Seven-segment, digital
Linear indicator, bar graph
Indication accuracy:
Four categories
Supply voltage:
Alternating current: 230 V
Direct current: 24 V
Power consumption:
Alternating current: ≤ 7.7 VА
Direct current: no more than 320 mA
Availability of a built-in power supply for inputs:
Yes, one channel
= 24 V, 25 mА
Non-volatile memory:
Yes, EEPROM
Galvanic isolation:
• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V
Installation type:
Shield
Case size (HxWxD):
96х96х120 mm
Weight, not more than:
не більше 0,5 kg
Degree of protection:
IP30
Ambient temperature: