Home Programmed logical controllers Controllers for small automation systems

- Programmable logic controller

МІК-50-17 - Programmable logic controller

Choose a modification:

Order code:

МІК-50-17
АА
Analog input signal type:
BB
Analog input signal type:
CC
Analog input signal type:
DD
Analog input signal type:
Ga
Power supply for passive sensors 0(4)-20mA:
С1
Type of the first analog output:
D
Type of discrete output signals:
U
Supply voltage:

Number:

Available for order.
  • Automatic regulation and logical control of technological processes
  • Mathematical, time, step and other functions
  • External signals are connected via terminals installed on the rear wall of the device
  • Without the possibility of connecting external expansion modules
Analog inputs:
  • quantity: 4
  • unified signals
  • voltage
  • resistance temperature transducers
  • thermocouples.
Discrete inputs:
  • quantity: 2
  • switching =24V
  • logical "0": 0-7V
  • logical "1": 19-32V
Feeding:
  • ~ 230 (+22 –33)V, (50 ± 1)Hz
  • = 24±4V
Analog outputs:
  • quantity: 1
  • unified signals.
Discrete outputs:
  • quantity: 4
  • OK transistor: up to 40V, 100mA
  • closing relay: up to 230V, 5A.
Interfaces:
  • RS-485
  • Modbus RTU protocol.
Seller

from

15 945

including VAT

Choose a modification and complete your order code

МІК-50-16

МІК-50-17

МІК-50-26

МІК-50-27

Additional features:

Expansion module:

Not supported

Not supported

Not supported

Not supported

Analog input signals:

Quantity of analog inputs:

4

4

8

8

Types of input sensors and signals:

0-5mА, 0(4)-20mА, 0-10V
0-50mВ, 0-200mВ, 0-1V
Pt(50P, 100P, gr21, Pt50, Pt100, Pt500, Pt1000), Cu(50, 100, гр.23)
Type L, Type K, Type S, Type B, Type A, Type J, Type E

0-5mА, 0(4)-20mА, 0-10V
0-50mВ, 0-200mВ, 0-1V
Pt(50P, 100P, gr21, Pt50, Pt100, Pt500, Pt1000), Cu(50, 100, гр.23)
Type L, Type K, Type S, Type B, Type A, Type J, Type E

0-5mА, 0(4)-20mА, 0-10V

0-5mА, 0(4)-20mА, 0-10V

Limit of the basic combined measurement error:

± 0,2 %

± 0,2 %

± 0,2 %

± 0,2 %

Рolling cycle time:

0.1 second

0.1 second

0.1 second

0.1 second

Galvanic isolation:

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Group. The output group is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Group. The output group is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

Analog output signals:

Quantity of analog outputs:

2

1

1

not included

Types of analog output signals:

0-5 mА , 0(4)-20 mА, 0-10V

0-5 mА , 0(4)-20 mА, 0-10V

0-5 mА , 0(4)-20 mА, 0-10V

not included

The limit of the main combined error of the output signal formation:

АО1: ±0,2 %
АО2: ±0,4 %

АО1: ±0,2 %

АО1: ±0,2 %

not included

Galvanic isolation:

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

not included

Discrete input signals:

Quantity of discrete inputs:

3

2

3

2

Trigger signal levels:

• Logical "0" signal - DISABLED state: 0-7 V
• Logical "1" signal - ON state: 18-30 V

• Logical "0" signal - DISABLED state: 0-7 V
• Logical "1" signal - ON state: 18-30 V

• Logical "0" signal - DISABLED state: 0-7 V
• Logical "1" signal - ON state: 18-30 V

• Logical "0" signal - DISABLED state: 0-7 V
• Logical "1" signal - ON state: 18-30 V

Input consumption:

≤ 10 mA

≤ 10 mA

-

-

Galvanic isolation:

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

Discrete output signals:

Quantity of discrete outputs:

5

4

5

4

Output types:

• Transistor OK: up to 40V, 100mA
• Closing relay: up to 220V, 5A

• Transistor OK: up to 40V, 100mA
• Switching relay (DO1, DO2): up to 220V, 8A
• Solid state relay (DO1 - DO4): up to 60V, 1.0AAC/ADC
• Closing relay (DO3, DO4): up to 220V, 5A

• Transistor OK: up to 40V, 100mA
• Closing relay: up to 220V, 5A

• Transistor OK: up to 40V, 100mA
• Switching relay (DO1, DO2): up to 220V, 8A
• Solid state relay (DO1 - DO4): up to 60V, 1.0AAC/ADC
• Closing relay (DO3, DO4): up to 220V, 5A

Galvanic isolation:

• Group. The output group is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Group. The output group is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

Indication:

Indication type:

Seven-segment, four-digit

Seven-segment, four-digit

Seven-segment, four-digit

Seven-segment, four-digit

Indication accuracy:

± 0,01 %

± 0,01 %

± 0,01 %

± 0,01 %

Interfaces:

Interface type:

RS-485

RS-485

RS-485

RS-485

Data exchange protocol:

Modbus-RTU (Slave mode)

Modbus-RTU (Slave mode)

Modbus-RTU (Slave mode)

Modbus-RTU (Slave mode)

Maximum line length within one network segment:

up to 1200 meters

up to 1200 meters

up to 1200 meters

up to 1200

Galvanic isolation:

• Full. The interface is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The input is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

Corps:

Installation type:

Shield

Shield

Shield

Shield

Case size (HxWxD):

96х96х186 mm

96х96х186 mm

96х96х186 mm

96х96х186 mm

Installation depth:

190 mm

190 mm

190 mm

190 mm

Weight, not more than:

1.0 kg

1.0 kg

1.0 kg

1.0 kg

Degree of protection:

IP30

IP30

IP30

IP30

Electrical data:

Supply voltage:

• Alternating current: ~ 230 (+22 V, -33 V) (50 ± 1) Hz
• Direct current: 24±4 V

• Alternating current: ~ 230 (+22 V, -33 V) (50 ± 1) Hz
• Direct current: 24±4 V

• Alternating current: ~ 230 (+22 V, -33 V) (50 ± 1) Hz
• Direct current: 24±4 V

• Alternating current: ~ 230 (+22 V, -33 V) (50 ± 1) Hz
• Direct current: 24±4 V

Power consumption:

• Alternating current: 13 VA
• Direct current: no more than 350 mA

• Alternating current: 13 VA
• Direct current: no more than 350 mA

• Alternating current: 13 VA
• Direct current: no more than 350 mA

• Alternating current: 13 VA
• Direct current: no more than 350 mA

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C

Premises of use:

closed explosion-proof, fire-proof

closed explosion-proof, fire-proof

closed explosion-proof, fire-proof

closed explosion-proof, fire-proof

Vibration:

with a frequency of up to 60 Hz with an amplitude of up to 0.1 mm

with a frequency of up to 60 Hz with an amplitude of up to 0.1 mm

with a frequency of up to 60 Hz with an amplitude of up to 0.1 mm

with a frequency of up to 60 Hz with an amplitude of up to 0.1 mm

Atmospheric pressure:

from 84 to 106.7 kPa

from 84 to 106.7 kPa

from 84 to 106.7 kPa

from 84 to 106.7 kPa