ITM-111 is a single-channel industrial indicator–measuring device designed for measuring temperature, pressure, humidity, flow, level, and other physical quantities in various industrial applications (depending on the connected sensor).

Functional features:

  • Measurement of temperature or other physical quantities (pressure, humidity, flow, level, etc.) using sensors with a standardized current or voltage output signal. Sensor type can be changed, calibration is required;
  • Digital filtering and input signal correction;
  • Scaling of the measurement range for each input;
  • Alarm function when the measured parameter goes beyond the specified range, with activation of discrete outputs;
  • Linear conversion of the input signal into a standardized analog output signal;
  • Indication of the measured value on a 4-digit, 7-segment display;
  • Integration into a dispatching system and data transmission to the upper level via RS-485 interface. Both Slave and Master modes are supported (can poll other devices via Modbus RTU protocol).
Input signals:
  • quantity: 1
  • unified signals
  • voltage
  • resistance temperature transducers
  • thermocouples
Analog output:
  • quantity: 1
  • unified signals
Discrete outputs:
  • quantity: 2
  • transistor OK: up to 40V, 100mA
  • relay: up to 230V, 8A.
Interfaces:
  • RS-485
  • Modbus RTU protocol
Power supply:
  • ~ 100 V to ~ 242 V, 6.5 VA
  • = 18 V to 36 V, 180 mА
Assembling:
  • panel
  • 48x96x141 mm
Seller

from

9 864

including VAT

Choose a modification and complete your order code

ІТМ-110

ІТМ-111

ІТМ-111В

General information:

Device type:

Technological indicator

Technological indicator

Technological indicator

Additional features:

Input signal conversion
Alarms

Input signal conversion
Alarms

Input signal conversion
Alarms

Analog input signals:

Quantity of analog inputs:

1

1

1

Types of input sensors and signals:

0-5 mA, 0-20 mA, 4-20 mA
0-75 mВ , 0-200 mВ , 0-2 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ, NTC (0-1 kΩ, 0-3 kΩ, 0-5 kΩ, 0-10 kΩ)

0-5 mA, 0-20 mA, 4-20 mA
0-75 mВ , 0-200 mВ , 0-2 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ, NTC (0-1 kΩ, 0-3 kΩ, 0-5 kΩ, 0-10 kΩ)

0-5 mA, 0-20 mA, 4-20 mA
0-75 mВ , 0-200 mВ , 0-2 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ, NTC (0-1 kΩ, 0-3 kΩ, 0-5 kΩ, 0-10 kΩ)

Limit of the basic combined measurement error:

≤ 0.2 %

≤ 0.2 %

≤ 0.2 %

Рolling cycle time:

up to 0.1 seconds

up to 0.1 seconds

up to 0.1 seconds

Galvanic isolation:

• Input isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Input isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Input isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

Switching to another sensor type:

User-configurable, calibration required

User-configurable, calibration required

User-configurable, calibration required

Discrete input signals:

Quantity of discrete inputs:

Not included

Not included

Not included

Analog output signals:

Number of outputs:

1

1

1

Output type:

active

active

active

Ranges of possible output signals:

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

The limit of the main combined error of the output signal formation:

≤ 0.2 %

≤ 0.2 %

≤ 0.2 %

Discrete output signals:

Quantity of discrete outputs:

2

2

2

Types of discrete outputs:

• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid State Relay (SSR): up to 60 V, 1 A

• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid State Relay (SSR): up to 60 V, 1 A

• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid State Relay (SSR): up to 60 V, 1 A

Interfaces:

Data exchange interface:

RS-485

RS-485

RS-485

Data exchange protocol:

Modbus RTU
Slave, master

Modbus RTU
Slave, master

Modbus RTU
Slave, master

Indication:

Indication type:

Seven-segment, digital

Seven-segment, digital
Linear indicator, bar graph

Seven-segment, digital
Linear indicator, bar graph

Indication accuracy:

Four categories

Four categories

Four categories

Electrical data:

Supply voltage:

Alternating current: 230 V
Direct current: 24 V

Alternating current: 230 V
Direct current: 24 V

Alternating current: 230 V
Direct current: 24 V

Power consumption:

Alternating current: ≤ 6.5 VА
Direct current: no more than 180 mA

Alternating current: ≤ 6.5 VА
Direct current: no more than 180 mA

Alternating current: ≤ 6.5 VА
Direct current: no more than 180 mA

Availability of a built-in power supply for inputs:

ption, provided that a 4..20mA signal is ordered
= 24 V, 25 mА

ption, provided that a 4..20mA signal is ordered
= 24 V, 25 mА

ption, provided that a 4..20mA signal is ordered
= 24 V, 25 mА

Non-volatile memory:

Yes, EEPROM

Yes, EEPROM

Yes, EEPROM

Galvanic isolation:

• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V

• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V

• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V

Corps:

Installation type:

Shield

Shield

Shield

Case size (HxWxD):

48х96х141 mm

48х96х141 mm

96х48х141 mm

Weight, not more than:

не більше 0,35 kg

не більше 0,35 kg

не більше 0,35 kg

Degree of protection:

IP30

IP30

IP30

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C