The BRG-112 galvanic isolation block is designed for:

  • 🛡 Galvanic protection of electrical circuits operating with standardized analog signals (current or voltage);
  • 🔄 Signal conversion and matching between different parts of measurement or control systems;
  • Increasing the reliability of automation and process control (SCADA/PCS) systems by protecting receiving devices from overvoltage, interference, and potential shifts.

The device provides galvanic isolation of the input signal from the output, effectively eliminating the influence of noise and potential differences between system segments.

Functional Features

  • 🔒 Galvanic isolation: complete electrical separation between input and output circuits;
  • 🛡 Signal protection: reduces the impact of transients, induced voltages, and electromagnetic interference;
  • 🔄 Signal conversion: transmits an analog signal from a passive input to a standardized active output, ready to connect to controllers, data loggers, or display devices;
  • Stability and accuracy: maintains the signal’s form and amplitude during isolation and conversion.

Electrical Characteristics

  • Input: 1 passive, standardized (current or voltage signal: 0–5 mA, 0–20 mA, 4–20 mA, or 0–10 V);
  • Output: 1 active, standardized (current or voltage signal for connection to a receiving device);
  • 🛡 Galvanic isolation: provides complete electrical separation between input and output;
  • 🔋 Power supply: 230 V or 24 V.
Input:
  • passive
  • unified
Output:
  • active
  • unified.
Power supply:
  • = 24 V, 100mA
  • ~230V, 5VA
Seller

from

4 128

including VAT

Choose a modification and complete your order code

BRG-11

BRG-670

BRG-671

BRG-112

Input signals:

Quantity inputs:

1

1

1

1

Input type:

passive

passive

active

passive

Possible input signal ranges/load resistance:

0 to 5 mA / R = 200 Ohm
0 to 20 mA / R ≤ 50 Ohm
4 to 20 mA / R ≤ 50 Ohm
0 to 10 V / R ≥ 20kOhm

4 to 20 mA / R ≤ 400 Ohm

0 to 5 mA / R = 200 Ohm
0 to 20 mA / R ≤ 50 Ohm
4 to 20 mA / R ≤ 62 Ohm
0 to 10 V / R ≥ 20kOhm

0 to 5 mA / R = 200 Ohm
0 to 20 mA / R ≤ 50 Ohm
4 to 20 mA / R ≤ 50 Ohm
0 to 10 V / R ≥ 20kOhm

Limit of the basic combined measurement error:

± 0,2 %

± 0,2 %

± 0,2 %

± 0,2 %

Output signals:

Quantity outputs:

1

1

1

1

Output type:

active

passive

passive

active

Ranges of possible output signals/load resistance:

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

4 to 20 mA R ≤ 800 Ohm

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

Galvanic isolation:

• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 2000 V.

• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

Electrical data:

Supply voltage:

Direct current: 24 V

Current loop, 24V

Direct current: 24 V

Direct current: 24 V
Alternating current: 230 V

Power consumption:

Direct current: no more than 125 mA

no more than 20mA

Direct current: no more than 30mA

Direct current: no more than 100 mA
Alternating current: no more than 5 VA

Corps:

Installation type:

on DIN rail

on DIN rail

on DIN rail

on DIN rail

Case size (HxWxD):

76х26х115 mm

94х7х64 mm

94х7х64 mm

100х23х115 mm

Weight, not more than:

0,13 kg

0,1 kg

0,1 kg

0,2 kg

Degree of protection:

IP20

IP20

IP20

IP20