THM-1
THM-11
Operating modes:
Tachometer
Operating time of units
Tachometer
Operating time of units
Number of counters:
one
one
Quantity of discrete inputs:
2
2
Maximum pulse frequency:
100 kHz
25 kHz (when forming a signal on the AO)
100 kHz
25 kHz (when forming a signal on the AO)
Minimum input pulse duration:
5 µs
5 µs
Input current (input consumption), no more:
5 mA
5 mA
Trigger signal levels:
Logical "0" signal – "DISABLED" state: 0-5V
Сигнал логічної "1" – стан "УВІМКНЕНО": 18-30V
Logical "0" signal – "DISABLED" state: 0-5V
Сигнал логічної "1" – стан "УВІМКНЕНО": 18-30V
Connectable sensors:
• Switching devices (contacts of buttons, switches, reed switches, relays, etc.)
• n-p-n-type with open collector output
• p-n-p-type
• Switching devices (contacts of buttons, switches, reed switches, relays, etc.)
• n-p-n-type with open collector output
• p-n-p-type
Quantity of discrete outputs:
2
2
Output types:
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid-state (non-mechanical) relay: 40 V, up to 0.5 A (AC/DC)
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid-state (non-mechanical) relay: 40 V, up to 0.5 A (AC/DC)
Load type:
Active
Inductive
Active
Inductive
Number of outputs:
1
Option, instead of DO1
1
Option, instead of DO1
Output type:
Active
Active
Ranges of possible output signals:
0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm
0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm
The limit of the main combined error of the output signal formation:
≤ 0.2%
≤ 0.2%
Indication type:
OLED display, 1.8"
Seven-segment
8th digit
Data exchange interface:
USB
RS-485
USB
RS-485
Data exchange protocol:
Modbus RTU
Modbus RTU
Supply voltage:
Direct current: 24 V
Alternating current: 230 V
Direct current: 24 V
Alternating current: 230 V
Power consumption:
Direct current: no more than 120 mA
Alternating current: no more than 1.5VA
Direct current: no more than 120 mA
Alternating current: no more than 1.5VA
Availability of a built-in power supply for inputs:
Yes, (option when ordering)
=24V, 30mA
Yes, (option when ordering)
=24V, 30mA
Galvanic isolation:
• Combined. Inputs have group isolation. Outputs, interface and power are isolated from other nodes and from each other.
• Galvanic isolation voltage is not less than 500 V.
• Combined. Inputs have group isolation. Outputs, interface and power are isolated from other nodes and from each other.
• Galvanic isolation voltage is not less than 500 V.
Installation type:
on DIN rail
shield
Case size (HxWxD):
100х55х60 mm
48х96х106 mm
Weight, not more than:
0,35 kg
0,35 kg
Degree of protection:
IP20
IP20
Ambient temperature:
-40 °C to +70 °C
-40 °C to +70 °C