Home Normalizing converters Resistance values:

- Блок перетворення сигналів величини опору, двоканальний, живлення токова петля

BPO-422 - Блок перетворення сигналів величини опору, двоканальний, живлення токова петля

Choose a modification:

Order code:

BPO-422
A
Initial value of the first measuring channel:
B
Final value of the first measuring channel:
C
Initial value of the second measuring channel:
D
Final value of the first measuring channel:

Number:

Available for order.

Potentiometric resistance signal conversion unit, two-channel:

 

  • Designed for linear conversion of resistance changes, in the range from 0 to 100kΩ, into a 4...20 mA current signal and power supply: current loop.
  • Sensor connection, two-wire or three-wire circuit.
  • Screw terminal block.
Inputs:
  • quantity: 2
  • Resistance in the range 0 - 100kΩ
  • two-wire connection
  • three-wire connection.
Outputs:
  • quantity: 2
  • 4-20mA
  • current loop
Power supply:
  • = 24 V
  • current loop.
Seller

from

4 962

including VAT

Choose a modification and complete your order code

BPO-420

BPO-422

Input signals:

Quantity inputs:

1

2

Input type:

Three-wire connection:
Two-wire connection

Three-wire connection:
Two-wire connection

Ranges of possible input signals:

Initial value of the input signal: 0 Ohm (arbitrary, but less than, at least 10% of the final value of the input signal)
Final input signal value: 100 Ohm to 100 kOhm

Initial value of the input signal: 0 Ohm (arbitrary, but less than, at least 10% of the final value of the input signal)
Final input signal value: 100 Ohm to 100 kOhm

Limit of the basic combined measurement error:

± 0,2 %

± 0,2 %

Measurement and conversion period:

0,01 second

0,01 second

Analog output signals:

Number of outputs:

1

2

Output type:

passive, current loop

passive, current loop

Ranges of possible output signals:

4 to 20 mA / R ≤ 500 Ohm

4 to 20 mA / R ≤ 500 Ohm

Discrete output signals:

Availability of discrete outputs:

No

No

Quantity of discrete outputs:

not included

not included

Types of discrete outputs:

not included

not included

Interfaces:

Data exchange interface:

not included

not included

Data exchange protocol:

not included

not included

Indication:

Digital display:

No

No

Electrical data:

Supply voltage:

Current loop, 24V

Current loop, 24V

Power consumption:

no more than 20 mA (channel)

no more than 20 mA (channel)

Non-volatile memory:

not included

not included

Galvanic isolation:

Missing.

Missing.

Corps:

Installation type:

on DIN rail

on DIN rail

Case size (HxWxD):

76х26х115 mm

76х26х115 mm

Weight, not more than:

0,13 kg

0,13 kg

Degree of protection:

IP20

IP20

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C