Home Meters-indicators Multi-channel meters-indicators:

Indicator - regulator, eight-channel

МТР-138 Indicator - regulator, eight-channel

Choose a modification:

Order code:

МТР-138
AA
Range of Eight Input Signals:
D
Discrete Output Signal Code:
E
Range of the first analog output:
R
Second analog output range:
S
Range of the third analog output:
T
Range of the fourth analog output:
U
Power Supply Voltage:

Number:

Available for order.

MTR-138 is an industrial-grade eight-channel digital indicator and controller designed for simultaneous measurement, indication, control, and remote monitoring of up to eight technological parameters such as temperature, pressure, humidity, flow, level, and other physical values (depending on the connected sensor). It provides output control signals for process automation.

⚙️ Functional Capabilities:

📊 Measurement and Indication:

  • 8 independent universal group-type inputs for measuring temperature or other physical parameters (pressure, humidity, flow, level, etc.) using sensors with a standardized current or voltage output signal. Sensor type change requires recalibration.
  • Real-time value display on a digital LED screen
  • Individual input signal scaling for each channel
  • Digital signal filtering and correction

🚨 Alarm Functions:

  • Alarm triggering when measured parameters exceed configured limits, activating discrete outputs
  • Linear conversion of the input signal into a standardized analog output signal

🔄 Additional Features:

  • Built-in mathematical functions
  • Communication interface: RS-485
  • Supported protocols: Modbus RTU

🔁 Control Functions:

  • Built-in control algorithms
  • ON/OFF control – basic threshold-based control for relays, valves, etc.
  • PID control – smooth and stable regulation of analog and discrete actuators
Input signals:
  • quantity: 8
  • unified signals
  • voltage
  • resistance temperature transducers
  • thermocouples
Discrete outputs:
  • quantity: 8
  • transistor OK: up to 40V, 100mA
  • relay: up to 230V, 5A.
Analog output:
  • quantity: 4
  • unified signals
Interfaces:
  • RS-485
  • Modbus RTU protocol
Power supply:
  • ~ 160 V to ~ 260 V, 5.8 VA
  • = 18 V to 36 V, 250 mА
Assembling:
  • panel
  • 96x96x135 mm
Seller

from

9 630

including VAT

Choose a modification and complete your order code

ІТМ-304

ІТМ-4

МТР-138

ІТМ-16

ІТМ-16Н

General information:

Device type:

Technological indicator

Technological indicator

Technological indicator

Technological indicator

Technological indicator

Additional features:

Input signal conversion
Alarms
Integration
Mathematical functions
Archiving

Input signal conversion
Alarms
Mathematical functions

Input signal conversion
Alarms
Mathematical functions
Regulation

Input signal conversion
Alarms

Input signal conversion
Alarms

Analog input signals:

Quantity of analog inputs:

4

4

8
group entry

16
group entry

16
group entry

Types of input sensors and signals:

0-5 mA, 0-20 mA, 4-20 mA, -5-5 mA, -20-20 mA
0-10 V, 0-100 mV, -10-10 V, -100-100 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,N,J,S,R,B,T,E,A-1, A-2, A-3
0-150 Ohm, 0-300 Ohm, 0-1200 Ohm, 0-2500 Ohm

0-5 mA, 0-20 mA, 4-20 mA
0-75 mВ , 0-200 mВ , 0-2 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ

0-5 mA, 0-20 mA, 4-20 mA
0-75mВ, 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt1000
Type: K,L,J,S,B,E,A-1
NTC 10 kOhm

0-5 mA, 0-20 mA, 4-20 mA
0-75 mV, 0-200mV, 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt1000
Type: K,L,J,S,B,E,A-1

0-5 mA, 0-20 mA, 4-20 mA
0-75 mV, 0-200mV, 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt1000
Type: K,L,J,S,B,E,A-1

Limit of the basic combined measurement error:

≤ 0.2 %
≤ 0.4 % (when switching to another sensor type, without calibration)

≤ 0.2 %

≤ 0.2 %

≤ 0.2 %

≤ 0.2 %

Рolling cycle time:

up to 0.1 seconds

up to 0.1 seconds

up to 0.1 seconds

up to 0.1 seconds

up to 0.1 seconds

Galvanic isolation:

• Input isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Input isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Group. Inputs are isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Group. Inputs are isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Group. Inputs are isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

Switching to another sensor type:

User-selectable sensor type switching. No calibration required.

User-configurable, calibration required

User-configurable, calibration required
Group input, one type for all inputs

User-configurable, calibration required
Group input, one type for all inputs

User-configurable, calibration required
Group input, one type for all inputs

Discrete input signals:

Quantity of discrete inputs:

Not included

Not included

Not included

In the basic: Not included
Depending on the expansion module model: maximum 32

In the basic: Not included
Depending on the expansion module model: maximum 32

Analog output signals:

Number of outputs:

1 (option)

1

up to 4 (option)

1 (expansion module only)

1 (expansion module only)

Output type:

active

active

active

active

active

Ranges of possible output signals:

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ

The limit of the main combined error of the output signal formation:

≤ 0.2 %

≤ 0.2 %

≤ 0.2 %

≤ 0.2 %

≤ 0.2 %

Discrete output signals:

Quantity of discrete outputs:

8 (optional)

4

8

In the basic: 2 (NPN transistor)
Depending on the expansion module model: maximum 32

In the basic: 2
Depending on the expansion module model: maximum 32

Types of discrete outputs:

• NPN transistor: up to 40V, 100mA
• Closing relays: up to 230V, 5A

• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Opto-triac: up to 300 V, 0.7 A

• NPN transistor: up to 40V, 100mA
• Closing relay: up to 230V, 5A

• NPN transistor: up to 40V, 100mA
• Closing relay: up to 230V, 5A

• NPN transistor: up to 40V, 100mA
• Closing relay: up to 230V, 5A

Interfaces:

Data exchange interface:

RS-485
USB
Ethernet

RS-485

RS-485

RS-485

RS-485

Data exchange protocol:

Modbus RTU
Modbus TCP

Modbus RTU
Slave

Modbus RTU
Slave

Modbus RTU
Slave

Modbus RTU
Slave

Indication:

Indication type:

Seven-segment, digital
4-digit display

Seven-segment, digital

Seven-segment, digital

Seven-segment, digital

Seven-segment, digital

Indication accuracy:

Four categories

Four categories

Four categories

Four categories

Four categories

Electrical data:

Supply voltage:

Alternating current: 230 V
Direct current: 24 V

Alternating current: 230 V
Direct current: 24 V

Alternating current: 230 V
Direct current: 24 V

Alternating current: 230 V
Direct current: 24 V

Alternating current: 230 V
Direct current: 24 V

Power consumption:

Direct current: no more than 400 mA
Alternating current: no more than 7 VA

Alternating current: ≤ 7.3 VА
Direct current: no more than 310 mA

Alternating current: ≤ 5.8 VА
Direct current: no more than 250 mA

Alternating current: ≤ 10 VА
Direct current: no more than 350 mA

Alternating current: ≤ 5 VА
Direct current: no more than 300 mA

Availability of a built-in power supply for inputs:

Yes, optional, if specified in the order
= 24 V, 25 mA (two channels)

ption, provided that a 4..20mA signal is ordered
= 24 V, 25 mА

Not included

Yes, optional, if specified in the order
= 24 V, 25 mA (two channels)

Not included

Non-volatile memory:

Yes, EEPROM

Yes, EEPROM

Yes, EEPROM

Yes, EEPROM

Yes, EEPROM

Galvanic isolation:

• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V

• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V

• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V

• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V

• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V

Corps:

Installation type:

Shield

Shield

Shield

Shield

DIN-rail

Case size (HxWxD):

96х96х153 mm

96х96х135 mm

96х96х135 mm

96х96х135 mm

110х160х58 mm

Weight, not more than:

не більше 0,25 kg

не більше 0,5 kg

не більше 1,0 kg

не більше 1,0 kg

не більше 0,5 kg

Degree of protection:

IP30

IP30

IP30

IP30

IP30

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C