Home Galvanic isolation and branching blocks Analog Signal Distributor / Splitter:

- Galvanic isolation unit

BRG-312 - Galvanic isolation unit

Choose a modification:

Order code:

BRG-312
AA
Input signal type:
С
Output signal type:
D
Output signal type:
U
Supply voltage:

Number:

Available for order.

BRG-312 — Galvanic Isolation and Signal Conversion Module

The BRG-312 is designed for galvanic isolation, normalization, and conversion of signals from various primary transducers into two independent analog output signals.

⚙️ Key Features

  • 🌡️ connection of Pt100, Pt500, Pt1000, TSP100, and TSM100 resistance temperature sensors;
  • 🔥 support for J, K, T, L, N, and S thermocouples;
  • 📈 operation with standardized current and voltage signals;
  • 💻 software selection of the input signal type;
  • 📊 signal scaling and normalization;
  • 🔁 two independent analog outputs;
  • 🛡️ galvanic isolation between the input, outputs, and power supply circuit;
  • ⚠️ detection of sensor circuit break, short circuit, and input signal out-of-range conditions;
  • 🔧 configuration via USB using Microl Configurator software.

⚡ Power Supply

  • 24 V DC;
  • 230 V AC.

📤 Analog Outputs

  • 4–20 mA;
  • 0–20 mA;
  • 0–5 mA;
  • 0–10 V.

🎯 The basic analog output accuracy is ±0.2% of the range.

🏭 Applications

The BRG-312 is used to transmit signals to controllers, regulators, indicators, recorders, SCADA systems, and other industrial automation equipment.

🔀 Two independent outputs allow the signal to be transmitted simultaneously to two different devices.

Inputs:
  • quantity: 1
  • unified signals
  • voltage
  • resistance temperature transducers
  • thermocouples.
Output:
  • 2
  • active
  • unified.
Power supply:
  • = 24 V, 150mA
  • ~=230V, 3.7VA
Assembling:
  • on DIN rail
  • 100x23x115 mm.
Interfaces:
  • USB (configuration)
  • Modbus RTU protocol.
Seller

7 140

including VAT

Choose a modification and complete your order code

BRG-13

BRG-122

BRG-312

Input signals:

Quantity inputs:

1

1

1

Input type:

passive

passive

passive

Possible input signal ranges/load resistance:

0 to 5 mA / R = 200 Ohm
0 to 20 mA / R ≤ 50 Ohm
4 to 20 mA / R ≤ 50 Ohm
0 to 10 V / R ≥ 20kOhm

0 to 5 mA / R = 200 Ohm
0 to 20 mA / R ≤ 50 Ohm
4 to 20 mA / R ≤ 50 Ohm
0 to 10 V / R ≥ 20kOhm

0-5 mA, 0-20 mA, 4-20 mA, -5-5 mA, -20-20 mA
0-10 V, 0-100 mV, -10-10 V, -100-100 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,N,J,S,R,B,T,E,A-1, A-2, A-3
0-150 Ohm, 0-300 Ohm, 0-1200 Ohm, 0-2500 Ohm

Limit of the basic combined measurement error:

± 0,2 %

± 0,2 %

± 0,2 %

Output signals:

Quantity outputs:

3

2

2

Output type:

active

active

active

Ranges of possible output signals/load resistance:

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

Galvanic isolation:

• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 1500 V.

• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.

Electrical data:

Supply voltage:

Direct current: 24 V

Direct current: 24 V
Alternating current: 230 V

Direct current: 24 V
Alternating current: 230 V

Power consumption:

Direct current: no more than 170 mA

Direct current: no more than 100 mA
Alternating current: no more than 5 VA

Direct current: no more than 150 mA
Alternating current: no more than 3.7 VA

Corps:

Installation type:

on DIN rail

on DIN rail

on DIN rail

Case size (HxWxD):

75х26х120 mm

100х23х115 mm

100х23х115 mm

Weight, not more than:

0,13 kg

0,2 kg

0,2 kg

Degree of protection:

IP20

IP20

IP20

Документація

Operating instructions BRG-312

Operating instructions BRG-312 1.4 MB PDF
UA
Програмне забезпечення

Installation archive, MicrolConfigurator, v1.008

Installation archive, MicrolConfigurator, v1.008 14.13 MB EXE
UA

Operating instructions , v1.01

Operating instructions , v1.01 1009.88 KB PDF
UA