Indicator - measuring device for technological parameters
ІТМ-100
ІТМ-101
ІТМ-101В
ІТМ-110
ІТМ-110Н
Device type:
Technological indicator
Technological indicator
Technological indicator
Technological indicator
Technological indicator
Additional features:
Input signal conversion
Alarms
Input signal conversion
Alarms
Input signal conversion
Alarms
Input signal conversion
Alarms
Input signal conversion
Alarms
Quantity of analog inputs:
1
1
1
1
1
Types of input sensors and signals:
0-5 mA, 0-20 mA, 4-20 mA
0-50 mВ , 0-100 mВ , 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ, NTC (0-1 kΩ, 0-3 kΩ, 0-5 kΩ, 0-10 kΩ)
0-5 mA, 0-20 mA, 4-20 mA
0-50 mВ , 0-100 mВ , 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ, NTC (0-1 kΩ, 0-3 kΩ, 0-5 kΩ, 0-10 kΩ)
0-5 mA, 0-20 mA, 4-20 mA
0-50 mВ , 0-100 mВ , 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ, NTC (0-1 kΩ, 0-3 kΩ, 0-5 kΩ, 0-10 kΩ)
0-5 mA, 0-20 mA, 4-20 mA
0-75 mВ , 0-200 mВ , 0-2 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ, NTC (0-1 kΩ, 0-3 kΩ, 0-5 kΩ, 0-10 kΩ)
0-5 mA, 0-20 mA, 4-20 mA
0-75 mВ , 0-200 mВ , 0-2 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ, NTC (0-1 kΩ, 0-3 kΩ, 0-5 kΩ, 0-10 kΩ)
Limit of the basic combined measurement error:
≤ 0.2 %
≤ 0.2 %
≤ 0.2 %
≤ 0.2 %
≤ 0.2 %
Рolling cycle time:
up to 0.1 seconds
up to 0.1 seconds
up to 0.1 seconds
up to 0.1 seconds
up to 0.1 seconds
Galvanic isolation:
Missing
Missing
Missing
• Input isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.
• Input isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.
Switching to another sensor type:
The sensor type is specified when ordering, switching to another type is not possible
The sensor type is specified when ordering, switching to another type is not possible
The sensor type is specified when ordering, switching to another type is not possible
User-configurable, calibration required
User-configurable, calibration required
Quantity of discrete inputs:
Not included
Not included
Not included
Not included
Not included
Number of outputs:
1 (option)
1 (option)
1 (option)
1
1
Output type:
active
active
active
active
active
Ranges of possible output signals:
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
The limit of the main combined error of the output signal formation:
≤ 0.2 %
≤ 0.2 %
≤ 0.2 %
≤ 0.2 %
≤ 0.2 %
Quantity of discrete outputs:
1 (optional)
1 (optional)
1 (optional)
2
2
Types of discrete outputs:
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid State Relay (SSR): up to 60 V, 1 A
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid State Relay (SSR): up to 60 V, 1 A
Data exchange interface:
RS-485
RS-485
RS-485
RS-485
RS-485
Data exchange protocol:
Modbus RTU
Modbus RTU
Modbus RTU
Modbus RTU
Slave, master
Modbus RTU
Slave, master
Indication type:
Seven-segment, digital
Seven-segment, digital
Linear indicator, bar graph
Seven-segment, digital
Linear indicator, bar graph
Seven-segment, digital
Seven-segment, digital
Indication accuracy:
Four categories
Four categories
Four categories
Four categories
Four categories
Supply voltage:
Alternating current: 230 V
Alternating current: 230 V
Alternating current: 230 V
Alternating current: 230 V
Direct current: 24 V
Alternating current: 230 V
Direct current: 24 V
Power consumption:
Alternating current: ≤ 4.0 VА
Alternating current: ≤ 4.0 VА
Alternating current: ≤ 4.0 VА
Alternating current: ≤ 6.5 VА
Direct current: no more than 180 mA
Alternating current: ≤ 6.5 VА
Direct current: no more than 180 mA
Availability of a built-in power supply for inputs:
ption, provided that a 4..20mA signal is ordered
= 24 V, 25 mА
ption, provided that a 4..20mA signal is ordered
= 24 V, 25 mА
ption, provided that a 4..20mA signal is ordered
= 24 V, 25 mА
ption, provided that a 4..20mA signal is ordered
= 24 V, 25 mА
ption, provided that a 4..20mA signal is ordered
= 24 V, 25 mА
Non-volatile memory:
Yes, EEPROM
Yes, EEPROM
Yes, EEPROM
Yes, EEPROM
Yes, EEPROM
Galvanic isolation:
• None for input signal. Output and interface are isolated from each other and power.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V
• None for input signal. Output and interface are isolated from each other and power.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V
• None for input signal. Output and interface are isolated from each other and power.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V
• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V
• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V
Installation type:
Shield
Shield
Shield
Shield
DIN-rail
Case size (HxWxD):
48х96х106 mm
48х96х106 mm
96х48х106 mm
48х96х141 mm
94х106х58 mm
Weight, not more than:
не більше 0,25 kg
не більше 0,25 kg
не більше 0,25 kg
не більше 0,35 kg
не більше 0,35 kg
Degree of protection:
IP30
IP30
IP30
IP30
IP30
Ambient temperature:
-40 °C to +70 °C
-40 °C to +70 °C
-40 °C to +70 °C
-40 °C to +70 °C
-40 °C to +70 °C