Home Normalizing converters Mechanism position (MEO):

- Actuator position transducer, inductive, inductive

PPM-2 - Actuator position transducer, inductive, inductive

Order code:

PPM-2
СС
Output signal type:
U
Supply voltage:

Number:

Available for order.

Pneumatic-electric signal conversion unit, with galvanic isolation:

  • Designed for continuous proportional conversion of the output shaft position signal of an electric actuator with an inductive sensor into unified current signals of 4...20 mA, 0...20 mA, 0...5 mA and voltage of 0...10 V.
  • Input signal measurement range: rotation of the inductive sensor shaft. The full stroke of the input signal corresponds to the angle of rotation of the profile cam of 0-225°(0-90°) of the mechanism sensor shaft.
  • Power supply: ~(230±22)V, = 24 V, 50mA.
  • Screw terminal block.
Inputs:
  • quantity: 1
  • degree of rotation of the inductive sensor shaft
Outputs:
  • quantity: 1
  • active
  • 0-5mA, 0(4)-20mA, 0-10V.
Power supply:
  • = 24 V, 80mA
  • ~230V, 4,5VA
Seller

from

5 766

including VAT

Choose a modification and complete your order code

PPM-2

Input signals:

Quantity inputs:

1

Input type:

Inductive sensor type
Three-wire connection

Ranges of possible input signals:

The full stroke of the input signal corresponds to the angle of rotation of the profile cam 0-225°(0-90°) of the mechanism sensor shaft

Limit of the basic combined measurement error:

± 2,5 %

Measurement and conversion period:

0,01 second

Analog output signals:

Number of outputs:

1

Output type:

active

Ranges of possible output signals:

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

Discrete output signals:

Availability of discrete outputs:

No

Quantity of discrete outputs:

not included

Types of discrete outputs:

not included

Interfaces:

Data exchange interface:

not included

Data exchange protocol:

not included

Indication:

Digital display:

No

Electrical data:

Supply voltage:

Direct current: 24 V
Alternating current: 230 V

Power consumption:

Direct current: no more than 120 mA
Alternating current: no more than 5 VA

Non-volatile memory:

not included

Galvanic isolation:

• Full. All components of the device are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.

Corps:

Installation type:

on DIN rail

Case size (HxWxD):

96х55х110 mm

Weight, not more than:

0,4 kg

Degree of protection:

IP30

Operating conditions:

Ambient temperature:

-40 °C to +70 °C