Touch operator panels Weintek
I/O modules
Spark protection barrier
Recorders and archivers
Meters and converters of electrical network parameters
Counters, timers, tachometers
Liquid level indicators and regulators
Programmed logical controllers
Manual signal transmitters
Technological signaling devices
Power supplies
Codesys PLC controllers
Galvanic isolation and branching blocks
Communication interface converters and amplifiers
Analytical instruments
Switching blocks
Control and protection units
GSM communication routers / modems
Indicator - measuring device for technological parameters, with circular scale
ІТМ-115
ІТМ-115Т
Device type:
Technological indicator
Technological indicator
Additional features:
Input signal conversion
Alarms
Input signal conversion
Alarms
Quantity of analog inputs:
1
1
Types of input sensors and signals:
0-5 mA, 0-20 mA, 4-20 mA
0-50 mВ , 0-100 mВ , 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ, NTC (0-1 kΩ, 0-3 kΩ, 0-5 kΩ, 0-10 kΩ)
0-5 mA, 0-20 mA, 4-20 mA
0-50 mВ , 0-100 mВ , 0-1 V, 0-10 V
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,J,S,B,E,A-1
0-1 kΩ, NTC (0-1 kΩ, 0-3 kΩ, 0-5 kΩ, 0-10 kΩ)
Limit of the basic combined measurement error:
≤ 0.2 %
≤ 0.25 % (for thermocouples)
≤ 0.2 %
≤ 0.25 % (for thermocouples)
Рolling cycle time:
up to 0.1 seconds
up to 0.1 seconds
Galvanic isolation:
• Input isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.
• Input isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.
Switching to another sensor type:
Sensor type can be changed by the user. Calibration is required after replacement.
Sensor type can be changed by the user. Calibration is required after replacement.
Quantity of discrete inputs:
Not included
Not included
Number of outputs:
1 (option)
1 (option)
Output type:
active
active
Ranges of possible output signals:
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
0 to 5 mA / R ≤ 2000 Ω
0 to 20 mA / R ≤ 500 Ω
4 to 20 mA / R ≤ 500 Ω
0 to 10 V / R ≤ 2 кΩ
The limit of the main combined error of the output signal formation:
≤ 0.2 %
≤ 0.2 %
Quantity of discrete outputs:
4
4
Types of discrete outputs:
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Opto-triac: up to 300 V, 0.7 A
• NPN transistor: up to 40V, 100mA
• Closing relays: up to 230V, 5A
Data exchange interface:
RS-485
RS-485
Data exchange protocol:
Modbus RTU
Modbus RTU
Indication type:
Seven-segment, digital
Circular scale
Seven-segment, digital
Circular scale
Indication accuracy:
Four categories
Four categories
Supply voltage:
Alternating current: 230 V
Direct current: 24 V
Alternating current: 230 V
Direct current: 24 V
Power consumption:
Alternating current: ≤ 8.5 VА
Direct current: 250 mА
Alternating current: ≤ 6.5 VА
Direct current: 250 mА
Availability of a built-in power supply for inputs:
Option, provided that a 4..20mA signal is ordered
= 24 V, 25 mА
Not included
Non-volatile memory:
Yes, EEPROM
Yes, EEPROM
Galvanic isolation:
• None for input signal. Output and interface are isolated from each other and power.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 1500 V
• Full. All components of the device are isolated from each other.
• Galvanic (electrical) isolation voltage (for outputs and interface), not less than 500 V
Installation type:
Shield
DIN rail
Wall mounting
Case size (HxWxD):
96х96х120 mm
145х120х80 mm
Weight, not more than:
не більше 0.6 kg
не більше 0.7 kg
Degree of protection:
IP30
IP65
Ambient temperature:
-40 °C to +70 °C
-40 °C to +70 °C