Touch operator panels Weintek
I/O modules
Spark protection barrier
Recorders and archivers
Meters and converters of electrical network parameters
Counters, timers, tachometers
Liquid level indicators and regulators
Programmed logical controllers
Manual signal transmitters
Technological signaling devices
Power supplies
Codesys PLC controllers
Galvanic isolation and branching blocks
Communication interface converters and amplifiers
Analytical instruments
Switching blocks
Control and protection units
GSM communication routers / modems
МТЛ-32
МТЛ-32H
Operating modes:
Pulse counter
Encoder, counter
Tachometer
Operating time of units
Timer
Flow meter
Pulse counter
Encoder, counter
Tachometer
Operating time of units
Timer
Flow meter
Number of counters:
one
one
Quantity of discrete inputs:
3
3
Maximum pulse frequency:
50 kHz
50 kHz
Minimum input pulse duration:
5 µs
5 µs
Input current (input consumption), no more:
5 mA
5 mA
Trigger signal levels:
Logical "0" signal – "DISABLED" state: 0-7V
Сигнал логічної "1" – стан "УВІМКНЕНО": 18-30V
Logical "0" signal – "DISABLED" state: 0-7V
Сигнал логічної "1" – стан "УВІМКНЕНО": 18-30V
Connectable sensors:
• Switching devices (contacts of buttons, switches, reed switches, relays, etc.)
• n-p-n-type with open collector output
• p-n-p-type
• Switching devices (contacts of buttons, switches, reed switches, relays, etc.)
• n-p-n-type with open collector output
• p-n-p-type
Quantity of discrete outputs:
2
2
Output types:
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid-state (non-mechanical) relay: 40 V, up to 0.5 A (AC/DC)
• NPN transistor: up to 40V, 100mA
• Switching relay: up to 230V, 8A
• Solid-state (non-mechanical) relay: 40 V, up to 0.5 A (AC/DC)
Load type:
Active
Inductive
Active
Inductive
Number of outputs:
1
Option, instead of DO1
1
Option, instead of DO1
Output type:
Active
Active
Ranges of possible output signals:
0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
The limit of the main combined error of the output signal formation:
≤ 0.2%
≤ 0.2%
Indication type:
Seven-segment
8th digit
Seven-segment
8th digit
Data exchange interface:
RS-485
RS-485
Data exchange protocol:
Modbus RTU
Modbus RTU
Supply voltage:
Direct current: 24 V
Alternating current: 230 V
Direct current: 12....36 V
Alternating current: 230 V
Power consumption:
Direct current 24V: no more than 250 mA
Direct current 36V: no more than 150 mA
Alternating current 230V: no more than 6VA
Direct current 24V: no more than 140 mA
Direct current 36V: no more than 150 mA
Alternating current 230V: no more than 5VA
Availability of a built-in power supply for inputs:
Yes, (option when ordering)
=24V, 30mA
Yes, (option when ordering)
=24V, 30mA
Galvanic isolation:
• Combined. Inputs have group isolation. Outputs, interface and power are isolated from other nodes and from each other.
• Galvanic isolation voltage is not less than 500 V.
• Combined. Inputs have group isolation. Outputs, interface and power are isolated from other nodes and from each other.
• Galvanic isolation voltage is not less than 500 V.
Installation type:
shield
DIN rail
Case size (HxWxD):
48х96х106 mm
110х106х58 mm
Weight, not more than:
0,35 kg
0,35 kg
Degree of protection:
IP20
IP20
Ambient temperature:
-40 °C to +70 °C
-40 °C to +70 °C