Touch operator panels Weintek
I/O modules
Spark protection barrier
Recorders and archivers
Meters and converters of electrical network parameters
Counters, timers, tachometers
Liquid level indicators and regulators
Programmed logical controllers
Manual signal transmitters
Technological signaling devices
Power supplies
Codesys PLC controllers
Galvanic isolation and branching blocks
Communication interface converters and amplifiers
Analytical instruments
Switching blocks
Control and protection units
GSM communication routers / modems
- Universal normalizing converter, single-channel
NPM-11
NPM-15
Quantity inputs:
1
1
Input type:
passive
passive
Ranges of possible input signals:
0-5 mA, 0-20 mA, 4-20 mA, -5-5 mA, -20-20 mA
0-10 V, 0-100 mV, -10-10 V, -100-100 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,N,J,S,R,B,T,E,A-1, A-2, A-3
0-150 Ohm, 0-300 Ohm, 0-1200 Ohm, 0-2500 Ohm
0-5 mA, 0-20 mA, 4-20 mA, -5-5 mA, -20-20 mA
0-10 V, 0-100 mV, -10-10 V, -100-100 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,N,J,S,R,B,T,E,A-1, A-2, A-3
0-150 Ohm, 0-300 Ohm, 0-1200 Ohm, 0-2500 Ohm
Limit of the basic combined measurement error:
± 0,2 %
± 0,2 %
Measurement and conversion period:
0,1 second
0,1 second
Number of outputs:
1
1
Output type:
active
active
Ranges of possible output signals:
0 to 5 mA (special version, reconfiguration to other signal types will be impossible)
0 to 20 mA
4 to 20 mA
0 to 10 V
0 mA to 5 mA (special version, reconfiguration to other signal types will be impossible)
0 to 20 mA
4 to 20 mA
0 to 10 V
Availability of discrete outputs:
Yes
Yes
Quantity of discrete outputs:
two
two
Types of discrete outputs:
• Closing relay: up to 230V, 5A
• Closing relay: up to 230V, 5A
Data exchange interface:
USB
RS-485
USB
RS-485
Data exchange protocol:
Modbus RTU
Modbus RTU
Digital display:
No
OLED, 1"
Supply voltage:
Direct current: 24 V
Alternating current: 230 V
Direct current: 24 V
Alternating current: 230 V
Power consumption:
Direct current: no more than 250 mA
Alternating current: no more than 5 VA
Direct current: no more than 100 mA
Alternating current: no more than 5 VA
Non-volatile memory:
Yes, EEPROM, NVRAM
Yes, EEPROM, NVRAM
Galvanic isolation:
• Full. All components of the device are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.
• Full. All components of the device are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.
Installation type:
on DIN rail
on DIN rail
Case size (HxWxD):
100х23х115 mm
110х23х115 mm
Weight, not more than:
0.3 kg
0.2 kg
Degree of protection:
IP20
IP20
Ambient temperature:
-40 °C to +70 °C
-40 °C to +70 °C