Home Normalizing converters Temperature sensor signals, analog:

- Thermoresistance signal conversion unit

BPO-644 - Thermoresistance signal conversion unit

Choose a modification:

Order code:

BPO-644
D
Type of sensor to be connected:
С
Symbol for the nominal static characteristic of the conversion:
W
Nominal value of the W100 ratio of the input signal:
N
Initial value of the measured temperature:
K
Final value of the measured temperature:
T
Output signal type:

Number:

Available for order.

Thermocouple signal conversion unit with galvanic isolation:

  • Designed to convert signals from resistance thermometers TSM 50M, TSM 100M, TSM 23 gr., Cu 50, Cu 100, TSP 50P, TSP 100P, TSP 21gr., Pt 50, Pt 100, Pt 500, Pt 1000 into universal current signals 4...20 mA, 0...20 mA, 0...5 mA and voltage 0...10 V.
  • Connection via input three-wire connection scheme.
  • Measured temperature ranges -200...+200 °C for copper thermometers and -200...+850 °C for platinum thermometers (depending on the type of resistance thermometer used).
  • Power supply 10-30V.
  • Spring terminal blocks.

 

Inputs:
  • quantity: 1
  • TSM, TSP, Pt
  • three-wire connection.
Outputs:
  • active
  • 0-5mA, 0(4)-20mA, 0-10V.
Power supply:
  • = 24 V, 30mA.
Seller

from

1 956

including VAT

Choose a modification and complete your order code

BPO-644

BPO-31

BPO-430

Input signals:

Quantity inputs:

1

1

1

Input type:

Three-wire connection:

Three-wire connection:

Three-wire connection:

Ranges of possible input signals:

Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt50, Pt100, Pt500, Pt1000

Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt50, Pt100

Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt50, Pt100

Limit of the basic combined measurement error:

± 0,25 %

± 0,25 %

± 0,2 %

Measurement and conversion period:

0,01 second

0,01 second

0,01 second

Analog output signals:

Number of outputs:

1

1

1

Output type:

active

active

passive, current loop

Ranges of possible output signals:

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 10000 Ohm

4 to 20 mA / R ≤ 500 Ohm

Discrete output signals:

Availability of discrete outputs:

No

No

No

Quantity of discrete outputs:

not included

not included

not included

Types of discrete outputs:

not included

not included

not included

Interfaces:

Data exchange interface:

not included

not included

not included

Data exchange protocol:

not included

not included

not included

Indication:

Digital display:

No

No

No

Electrical data:

Supply voltage:

Direct current: 24 V

Direct current: 24 V

Current loop, 24V

Power consumption:

Direct current: no more than 30 mA

Direct current: no more than 110 mA

no more than 20 mA (channel)

Non-volatile memory:

not included

not included

not included

Galvanic isolation:

• Missing

• Full. All components of the device are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.

Missing.

Corps:

Installation type:

on DIN rail

on DIN rail

on DIN rail

Case size (HxWxD):

94х7х64 mm

76х26х115 mm

76х26х115 mm

Weight, not more than:

0,1 kg

0,1 kg

0,13 kg

Degree of protection:

IP20

IP20

IP20

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C

-40 °C to +70 °C