Home Normalizing converters Thermosensor signals, microprocessor:

- Universal normalizing converter, single-channel

NPM-12 - Universal normalizing converter, single-channel

Choose a modification:

Order code:

NPM-12
AA
Input signal type:
CC
Output signal type:

Number:

Available for order.

Universal standardizing converter NPM-612, - is designed to convert temperature values ​​measured using a thermocouple or resistance thermometers or standardized signals (pressure, flow) into universal current signals 4...20 mA, 0...20 mA, 0...5 mA and voltage 0...10 V.
The converter allows switching between different types of sensors without the need for calibration.
It is configured using the MIC-Programmer software package via one of the built-in USB interfaces. Configuration parameters are stored in non-volatile memory.
Partial galvanic isolation (protection) is provided. The input and power supply of the device are isolated from each other. The output is not isolated.

Inputs:
  • quantity: 1
  • unified signals
  • voltage
  • resistance temperature transducers
  • thermocouples.
Analog outputs:
  • quantity: 1
  • unified signals.
Power supply:
  • = 24 V, 60mA.
Interfaces:
  • USB (configuration).
Assembling:
  • on DIN rail
  • 91x15x64 mm.
Seller

from

4 584

including VAT

Choose a modification and complete your order code

NPM-12

NPM-12

Input signals:

Quantity inputs:

1

1

Input type:

passive

passive

Ranges of possible input signals:

0-5 mA, 0-20 mA, 4-20 mA, -5-5 mA, -20-20 mA
0-10 V, 0-100 mV, -10-10 V, -100-100 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,N,J,S,R,B,T,E,A-1, A-2, A-3
0-150 Ohm, 0-300 Ohm, 0-1200 Ohm, 0-2500 Ohm

0-5 mA, 0-20 mA, 4-20 mA, -5-5 mA, -20-20 mA
0-10 V, 0-100 mV, -10-10 V, -100-100 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,N,J,S,R,B,T,E,A-1, A-2, A-3
0-150 Ohm, 0-300 Ohm, 0-1200 Ohm, 0-2500 Ohm

Limit of the basic combined measurement error:

± 0,2 %
± 0.2 mm

± 0,2 %

Measurement and conversion period:

0,1 second

0,1 second

Analog output signals:

Number of outputs:

1

1

Output type:

active

active

Ranges of possible output signals:

0 to 5 mA (special version, reconfiguration to other signal types will be impossible)
0 to 20 mA
4 to 20 mA
0 to 10 V

0 to 5 mA (special version, reconfiguration to other signal types will be impossible)
0 to 20 mA
4 to 20 mA
0 to 10 V

Discrete output signals:

Availability of discrete outputs:

No

No

Quantity of discrete outputs:

not included

not included

Types of discrete outputs:

not included

not included

Interfaces:

Data exchange interface:

USB

USB

Data exchange protocol:

Modbus RTU

Modbus RTU

Indication:

Digital display:

No

No

Electrical data:

Supply voltage:

Direct current: 24 V

Direct current: 24 V

Power consumption:

Direct current: no more than 60 mA

Direct current: no more than 60 mA

Non-volatile memory:

Yes, EEPROM, NVRAM

Yes, EEPROM, NVRAM

Galvanic isolation:

• Full. All components of the device are isolated from each other.
• Galvanic isolation voltage is not less than 500 V.

• Partially. The input and power supply of the device are isolated from each other. The output is not isolated.
• Galvanic isolation voltage is not less than 500 V.

Corps:

Installation type:

on DIN rail

on DIN rail

Case size (HxWxD):

99х13х115 mm

91x15x64 mm

Weight, not more than:

0.3 kg

0.3 kg

Degree of protection:

IP20

IP20

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C