Home Normalizing converters Temperature sensor signals, analog:

- Thermoresistance signal conversion unit, dual-channel

BPO-132 - Thermoresistance signal conversion unit, dual-channel

Choose a modification:

Order code:

BPO-132
D
Type of sensor to be connected:
С
Symbol for the nominal static characteristic of the conversion:
W
Nominal value of the W100 ratio of the input signal:
N
Initial value of the measured temperature:
K
Final value of the measured temperature:
T
Output signal type:

Number:

Available for order.

Thermoresistance signal conversion unit with galvanic isolation, dual-channel:

  • Designed to convert signals from resistance thermometers TSM 50M, TSM 100M, TSM 23 gr., Cu 50, Cu 100, TSP 50P, TSP 100P, TSP 21gr., Pt 50, Pt 100 into universal current signals 4...20 mA, 0...20 mA, 0...5 mA and voltage 0...10 V.
  • Two separate, independent measurement and conversion channels.
  • Connection via input three-wire connection scheme.
  • Measured temperature ranges -200...+200 °C for copper thermometers and -200...+850 °C for platinum thermometers (depending on the type of resistance thermometer used).
  • Power supply 10-30V.
  • Screw terminal block.

 

Inputs:
  • quantity: 2
  • TSM, TSP, Pt
  • three-wire connection.
Outputs:
  • 2
  • active
  • 0-5mA, 0(4)-20mA, 0-10V.
Power supply:
  • = 24 V, 110mA.
Seller

from

4 398

including VAT

Choose a modification and complete your order code

BPO-132

BPO-432

Input signals:

Quantity inputs:

2

2

Input type:

Three-wire connection:

Three-wire connection:

Ranges of possible input signals:

Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt50, Pt100

Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt50, Pt100

Limit of the basic combined measurement error:

± 0,25 %

± 0,25 %

Measurement and conversion period:

0,01 second

0,01 second

Analog output signals:

Number of outputs:

2

2

Output type:

active

passive, current loop

Ranges of possible output signals:

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 10000 Ohm

4 to 20 mA / R ≤ 500 Ohm

Discrete output signals:

Availability of discrete outputs:

No

No

Quantity of discrete outputs:

not included

not included

Types of discrete outputs:

not included

not included

Interfaces:

Data exchange interface:

not included

not included

Data exchange protocol:

not included

not included

Indication:

Digital display:

No

No

Electrical data:

Supply voltage:

Direct current: 24 V

Current loop, 24V

Power consumption:

Direct current: no more than 110 mA

no more than 20 mA (channel)

Non-volatile memory:

not included

not included

Galvanic isolation:

• Inputs and outputs are not isolated from each other, but isolated from the power supply circuit
• Galvanic isolation voltage is not less than 500 V.

• The channels are isolated from each other. The input is not isolated from the output.
• Galvanic isolation voltage is not less than 500 V.

Corps:

Installation type:

on DIN rail

on DIN rail

Case size (HxWxD):

76х26х115 mm

76х26х115

Weight, not more than:

0,1 kg

0,13 kg

Degree of protection:

IP20

IP20

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C