Home Manual signal transmitters Analog: manual control units:

- Manual control unit, analog

БРУ-1 - Manual control unit, analog

Choose a modification:

Order code:

БРУ-1
BB
Output signal code:

Number:

Available for order.

The BRU-1 device is intended for manual control of an analog actuator or a setter of a unified analog signal. It provides the formation of a unified signal: 0..5 mA, 0(4)…20 mA or 0…10 V, the value of which is set by the user from the front panel.

Functionality:

  • Output signal: 0..5 mA, 0(4)…20 mA or 0…10 V (modifications);
  • Power supply =24 V;
  • Mounting in a panel;
  • Galvanic isolation.
Output:
  • quantity: 1
  • active
  • 0-5mA, 0(4)-20mA, 0-10V.
Power supply:
  • = 24 V, 75mA.
Assembling:
  • panel
  • 48x48x143 mm.
Seller

4 680

including VAT

БРУ-1

БРУ-420

Analog output signals:

Quantity of analog outputs:

1

1

Ranges of possible output signals/load resistance:

0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm

4 to 20 mA / R ≤ 500 Ohm

The limit of the main combined error of the output signal formation:

±2,0%

±2,0%

Corps:

Case size (HxWxD):

48х48х143 mm

48х48х140 mm

Degree of protection:

IP30

IP30

Electrical data:

Supply voltage:

Direct current: 24 V

Direct current: 24 V
Current loop

Power consumption:

Direct current: no more than 75 mА

Direct current: no more than 25 mА

Operating conditions:

Ambient temperature:

-40 °C to +70 °C

-40 °C to +70 °C