- Galvanic isolation unit
BRG-311
Quantity inputs:
1
Input type:
passive
Possible input signal ranges/load resistance:
0-5 mA, 0-20 mA, 4-20 mA, -5-5 mA, -20-20 mA
0-10 V, 0-100 mV, -10-10 V, -100-100 mV
Cu 50, Cu 100, Pt 50P, Pt 100P, Pt50, Pt100, Pt500, Pt1000
Type: K,L,N,J,S,R,B,T,E,A-1, A-2, A-3
0-150 Ohm, 0-300 Ohm, 0-1200 Ohm, 0-2500 Ohm
Limit of the basic combined measurement error:
± 0,2 %
Quantity outputs:
1
Output type:
active
Ranges of possible output signals/load resistance:
0 to 5 mA / R = 2000 Ohm
0 to 20 mA / R ≤ 500 Ohm
4 to 20 mA / R ≤ 500 Ohm
0 to 10 V / R ≥ 2000 Ohm
Galvanic isolation:
• Full. The output is isolated from other circuits.
• Galvanic isolation voltage is not less than 500 V.
Supply voltage:
Direct current: 24 V
Alternating current: 230 V
Power consumption:
Direct current: no more than 150 mA
Alternating current: no more than 3.7 VA
Installation type:
on DIN rail
Case size (HxWxD):
100х23х115 mm
Weight, not more than:
0,2 kg
Degree of protection:
IP20
Operating instructions BRG-311