БІЗ-21-АО1
БІЗ-21-АО2
Intrinsic Safety Level of the Electrical Circuit:
II(1)G[ExiaGa]IIC
II(1)G[ExiaGa]IIC
Number of protection circuits in the barrier:
1
1
Barrier type:
passive
passive
The maximum permissible voltage value (Um) at which the intrinsic safety of the circuit is ensured:
250 V
250 V
Designed to protect:
0..5 mА
0..10 V
RS-485
Discrete signals, 24V to 10mA
0..20 mА
4..20 mА
Maximum barrier output voltage (U0):
31.4 V
31.4 V
Maximum barrier output current (I0):
50 mА
90 mА
Barrier resistance:
From 660 to 700 Ohms
From 450 to 550 Ohms
Resistance of one branch of the barrier:
From 330 to 350 Ohms
From 330 to 350 Ohms
The difference in resistance between the branches:
Not normalized
Not normalized
Maximum permissible capacitance of the protected circuit (C0):
0.055 μF
0.055 μF
Maximum permissible inductance of the protected circuit (L0):
1.5 mH
0.7 mH
Fuse operating current:
50 mА
50 mА
Leakage current for input voltage, no more than:
= 24 V: 5 μA
= 4 V : 1 μA
= 0.1 V: 0.1 μA
= 24 V: 5 μA
= 4 V : 1 μA
= 0.1 V: 0.1 μA
Installation type:
DIN-rail
DIN-rail
Overall dimensions:
82х23х99 mm
82х23х99 mm
Ambient temperature:
-40 °C to +70 °C
-40 °C to +70 °C